Find the correct wire gauge for your 220V circuit. Enter the load current in amps, the one-way cable run length, and your maximum allowable voltage drop. The calculator returns the minimum AWG and nearest metric mm² size that keeps voltage drop within your limit.
Results cover standard copper conductor sizes. Always have fixed wiring installed by a licensed electrician in accordance with your local wiring code.
| AWG | mm² | Resistance (ohm/m) | Voltage Drop | Drop % | Status |
|---|
Selecting the correct wire size for a 220 volt circuit comes down to two things: the wire must carry the load current without overheating, and the resistance of the cable must not cause more voltage drop than your equipment can tolerate. This calculator applies both checks. It first requires a conductor whose typical current rating meets your load, then sizes up further if the voltage drop would otherwise exceed your limit, and recommends the larger of the two. Voltage drop is usually the binding factor on branch circuit runs of 10 metres or more, while the current rating is the deciding factor on shorter runs.
The voltage drop across a two-conductor cable is calculated as:
Voltage Drop = 2 x L x I x (rho / A)
Where L is the one-way cable length in metres, I is the current in amps, rho is the conductor resistivity (0.01724 ohm·mm²/m for copper, 0.02826 for aluminium), and A is the conductor cross-sectional area in mm². The factor of 2 accounts for the current travelling both ways through the circuit (outward on the live conductor and back through the neutral or return conductor). For split-phase 220V (two live conductors), the same formula applies. For three-phase, the factor changes to the square root of 3 (approximately 1.732).
Rearranging to find the minimum cross-section required to stay within a given voltage drop limit:
A (min) = 2 x L x I x rho / V_drop_max
where V_drop_max = (drop% / 100) x supply voltage.
| AWG | Area (mm²) | Nearest metric (mm²) | Resistance (copper, ohm/m) | Typical maximum current |
|---|---|---|---|---|
| 14 | 2.08 | 2.5 mm² | 0.00829 | 15 A |
| 12 | 3.31 | 4 mm² | 0.00521 | 20 A |
| 10 | 5.26 | 6 mm² | 0.00328 | 30 A |
| 8 | 8.37 | 10 mm² | 0.00206 | 40 A |
| 6 | 13.3 | 16 mm² | 0.00130 | 55 A |
| 4 | 21.2 | 25 mm² | 0.000814 | 70 A |
| 2 | 33.6 | 35 mm² | 0.000513 | 95 A |
| 1/0 | 53.5 | 50 mm² | 0.000322 | 125 A |
| 2/0 | 67.4 | 70 mm² | 0.000256 | 145 A |
Default inputs: 220V supply, 20 A load, 15 m one-way cable run, single-phase, 3% voltage drop limit, copper conductors.
Maximum allowable voltage drop = 3% x 220 V = 6.6 V.
Required minimum cross-section for voltage drop = (2 x 15 x 20 x 0.01724) / 6.6 = 10.344 / 6.6 = 1.567 mm².
By voltage drop alone, the next standard AWG size above 1.567 mm² would be 14 AWG (2.08 mm²). But 14 AWG has a typical maximum current of only 15 A, below the 20 A load, so it cannot safely carry the current. The calculator therefore steps up to the smallest size rated for at least 20 A, which is 12 AWG (3.31 mm², nearest metric 4 mm²).
Actual voltage drop with 12 AWG = 2 x 15 x 20 x (0.01724 / 3.31) = 10.344 / 3.31 = 3.13 V, which is 1.42% of 220 V, comfortably within the 3% limit.
This matches what the calculator shows for the default settings.
Most electrical codes recommend keeping voltage drop to 3% or less on branch circuits, and 5% or less over the combined feeder and branch circuit. For 220V, 3% equals 6.6V and 5% equals 11V. Sensitive equipment such as computers, motors, and variable speed drives typically performs best with voltage drop below 2%. New Zealand's AS/NZS 3000 Wiring Rules do not specify a single percentage limit but note that voltage drop should not adversely affect equipment operation; in practice, 5% is widely used as the design maximum.
This calculator provides sizing guidance based on voltage drop plus a basic current-rating check against the typical maximum current for each gauge. It does not apply the full ampacity derating required in practice. Actual wire selection must also consider the detailed current-carrying capacity (ampacity) of the conductor, ambient temperature, number of conductors bundled together, conduit fill, and any applicable local wiring code requirements. In New Zealand, all fixed 220V/230V/240V wiring must be installed by a licensed electrical worker (LEW) in accordance with AS/NZS 3000. Never attempt fixed wiring yourself unless you hold the appropriate licence.
Sources and method: Conductor resistivity values from IEC 60228 (Conductors of insulated cables). Wire size cross-reference from ASTM B258 (AWG) and IEC 60228 standard metric sizes. Voltage drop formula per AS/NZS 3000 Wiring Rules guidance. AWG cross-sections from NIST Handbook of Mathematical Functions. Current-carrying capacity guidance from AS/NZS 3008.1.1.
This calculator is for guidance only and covers voltage drop plus a basic current-rating check for copper or aluminium conductors. It does not substitute for a full electrical design. Actual cable selection must account for full ampacity derating, installation method, ambient temperature, and compliance with applicable wiring codes. Always consult a licensed electrical worker for any fixed wiring installation.
If you've found a bug, or would like to contact us, or learn more about James Graham and Calculate.co.nz.
Calculate.co.nz is partnered with Interest.co.nz for New Zealand's highest quality calculators and financial analysis.
Calculate.co.nz is the sister site of CalculatorHub.com, the world's largest calculator website by tool count.
All calculators and tools are provided for educational and indicative purposes only and do not constitute financial advice.
Calculate.co.nz is proudly part of the Realtor.co.nz group, New Zealand's leading property transaction literacy platform, helping Kiwis understand the home buying and selling process from start to finish. Whether you're a first home buyer navigating your first property purchase, an investor evaluating your next acquisition, or a homeowner planning to sell, Realtor.co.nz provides clear, independent, and trustworthy guidance on every step of the New Zealand property transaction journey.
Calculate.co.nz is also partnered with Health Based Building and Premium Homes to promote informed choices that lead to better long-term outcomes for Kiwi households.
Calculate.co.nz is hosted in Auckland via SiteHost new Zealand.
All content on this website, including calculators, tools, source code, and design, is protected under the Copyright Act 1994 (New Zealand). No part of this site may be reproduced, copied, distributed, stored, or used in any form without prior written permission from the owner.
About & trust: Why Calculate is NZ's most comprehensive · By the Numbers · How we compare · Editorial standards · How we keep data current · NZ finance glossary · Research & data · Financial literacy NZ · About · Privacy policy · Terms of use
Reviewed and maintained. Last reviewed 2026-07-02 and checked on a twice-monthly cycle against IRD, RBNZ and Stats NZ. How we keep data current.
© 2026 Calculate.co.nz. All rights reserved. Building free NZ calculators since 2011.