220 Volt Wire Size Calculator

This calculator works out the minimum wire size you need for a 220 volt (or 230V/240V) electrical circuit, balancing two safety requirements: the cable must carry your load current without overheating, and its resistance must not cause more voltage drop than your equipment can tolerate. Enter your supply voltage, the load current in amps, the one-way length of the cable run in metres, your circuit type (single-phase, split-phase 220V, or three-phase), the maximum voltage drop you can accept (typically 3% for branch circuits or 5% for feeders), and whether your conductors are copper or aluminium. The calculator returns the minimum AWG gauge and its nearest metric mm² equivalent, plus the actual voltage drop in volts and as a percentage of your supply voltage at that wire size. A comparison table below the results lists every standard wire size with its resistance, voltage drop and pass or fail status, so you can see why a given gauge was chosen and how much headroom the next size up gives you. Use it when planning a fixed 220V/230V/240V circuit, extending a cable run, or checking whether an existing wire is adequate for a higher load. Results are an indicative guide based on voltage drop and a basic current rating check only, not full ampacity derating or a qualified electrical design, so always have fixed wiring installed and verified by a licensed electrician.

Calculate.co.nz is proud to be partnered with Health Based Building, a leader in sustainable and health-conscious building innovation. With over a century of experience, they develop high-performance systems like Foreverbreathe Specification, Magnum Board, and Foreverbreathe Paints to support energy-efficient, non-toxic living environments. Their commitment to healthier homes aligns with our belief that informed choices lead to better outcomes for Kiwi households.
Calculate.co.nz partner: Health Based Building
Advertise on this page
Updated  Based on copper resistivity 0.01724 ohm·mm²/m and standard AWG/metric cross-reference tables.

1. Circuit Details

A
m

2. Voltage Drop Limit

Recommended Wire Size

Minimum AWG
12 AWG
Copper gauge required
Minimum mm²
4 mm2
Metric cross-section
Voltage Drop
3.13 V
At selected wire size
Drop Percentage
1.42%
Of supply voltage

Wire Size Comparison Table

AWGmm²Resistance (ohm/m)Voltage DropDrop %Status

Calculation Breakdown

Supply voltage220 V
Load current20 A
One-way cable length15 m
Total conductor length30.00 m (factor 2)
Circuit typeSingle-phase
Conductor materialCopper
Max allowable drop6.60 V (3% of 220 V)
Required cross-section1.567 mm2 minimum

Recommended Wire Size

Selected AWG12 AWG
Nearest metric size4 mm2
Actual cross-section3.31 mm2
Resistance (ohm/m)0.00521 ohm/m
Voltage drop3.13 V
Drop as % of supply1.42%
Within limit?Yes
Result: Enter your circuit details above.

How to Calculate Wire Size for a 220V Circuit

Selecting the correct wire size for a 220 volt circuit comes down to two things: the wire must carry the load current without overheating, and the resistance of the cable must not cause more voltage drop than your equipment can tolerate. This calculator applies both checks. It first requires a conductor whose typical current rating meets your load, then sizes up further if the voltage drop would otherwise exceed your limit, and recommends the larger of the two. Voltage drop is usually the binding factor on branch circuit runs of 10 metres or more, while the current rating is the deciding factor on shorter runs.

The voltage drop across a two-conductor cable is calculated as:

Voltage Drop = 2 x L x I x (rho / A)

Where L is the one-way cable length in metres, I is the current in amps, rho is the conductor resistivity (0.01724 ohm·mm²/m for copper, 0.02826 for aluminium), and A is the conductor cross-sectional area in mm². The factor of 2 accounts for the current travelling both ways through the circuit (outward on the live conductor and back through the neutral or return conductor). For split-phase 220V (two live conductors), the same formula applies. For three-phase, the factor changes to the square root of 3 (approximately 1.732).

Rearranging to find the minimum cross-section required to stay within a given voltage drop limit:

A (min) = 2 x L x I x rho / V_drop_max

where V_drop_max = (drop% / 100) x supply voltage.

Standard Wire Sizes: AWG vs Metric (mm²)

AWGArea (mm²)Nearest metric (mm²)Resistance (copper, ohm/m)Typical maximum current
142.082.5 mm²0.0082915 A
123.314 mm²0.0052120 A
105.266 mm²0.0032830 A
88.3710 mm²0.0020640 A
613.316 mm²0.0013055 A
421.225 mm²0.00081470 A
233.635 mm²0.00051395 A
1/053.550 mm²0.000322125 A
2/067.470 mm²0.000256145 A

Worked Example

Default inputs: 220V supply, 20 A load, 15 m one-way cable run, single-phase, 3% voltage drop limit, copper conductors.

Maximum allowable voltage drop = 3% x 220 V = 6.6 V.

Required minimum cross-section for voltage drop = (2 x 15 x 20 x 0.01724) / 6.6 = 10.344 / 6.6 = 1.567 mm².

By voltage drop alone, the next standard AWG size above 1.567 mm² would be 14 AWG (2.08 mm²). But 14 AWG has a typical maximum current of only 15 A, below the 20 A load, so it cannot safely carry the current. The calculator therefore steps up to the smallest size rated for at least 20 A, which is 12 AWG (3.31 mm², nearest metric 4 mm²).

Actual voltage drop with 12 AWG = 2 x 15 x 20 x (0.01724 / 3.31) = 10.344 / 3.31 = 3.13 V, which is 1.42% of 220 V, comfortably within the 3% limit.

This matches what the calculator shows for the default settings.

Voltage Drop Limits

Most electrical codes recommend keeping voltage drop to 3% or less on branch circuits, and 5% or less over the combined feeder and branch circuit. For 220V, 3% equals 6.6V and 5% equals 11V. Sensitive equipment such as computers, motors, and variable speed drives typically performs best with voltage drop below 2%. New Zealand's AS/NZS 3000 Wiring Rules do not specify a single percentage limit but note that voltage drop should not adversely affect equipment operation; in practice, 5% is widely used as the design maximum.

Safety Note

This calculator provides sizing guidance based on voltage drop plus a basic current-rating check against the typical maximum current for each gauge. It does not apply the full ampacity derating required in practice. Actual wire selection must also consider the detailed current-carrying capacity (ampacity) of the conductor, ambient temperature, number of conductors bundled together, conduit fill, and any applicable local wiring code requirements. In New Zealand, all fixed 220V/230V/240V wiring must be installed by a licensed electrical worker (LEW) in accordance with AS/NZS 3000. Never attempt fixed wiring yourself unless you hold the appropriate licence.

Related Calculators

Sources and method: Conductor resistivity values from IEC 60228 (Conductors of insulated cables). Wire size cross-reference from ASTM B258 (AWG) and IEC 60228 standard metric sizes. Voltage drop formula per AS/NZS 3000 Wiring Rules guidance. AWG cross-sections from NIST Handbook of Mathematical Functions. Current-carrying capacity guidance from AS/NZS 3008.1.1.

This calculator is for guidance only and covers voltage drop plus a basic current-rating check for copper or aluminium conductors. It does not substitute for a full electrical design. Actual cable selection must account for full ampacity derating, installation method, ambient temperature, and compliance with applicable wiring codes. Always consult a licensed electrical worker for any fixed wiring installation.